HMWST-C2 type intelligent temperature controller
WST-C2 type intelligent temperature controller introduction
The function of each button is clearly, through the relay hige to achieve automatic control, temperature controller will according to the changes and automatically shut off or start the control equipment.
1. Technical specifications:
Temperature measurement range: | 0-125degree | ||
Sensor: | DS18B20 | ||
Resolution: | 0.1degree | ||
The control accuracy: | 0.1 degree | ||
Output type: | relay (contacts capacity of 250 V, 5A), | ||
Shell size: | 87 mm *135 mm *45 mm | ||
Working voltage: | AC85 ~ 242 V 50 Hz / 60 Hz | ||
Types of control: | Heating-type | Cold-type | Automatic heating/cold type |
2. The parameters set operation:
Shows an energized observation, not changing the set, the original record the data set with automatic control operationChange is accused of temperature setting: It is energized, long press SET key, access to menu mode, according to the corresponding parameters on the adjustment, press " increase " or " reduce " button to change the SET value, " increase " is used to increase the temperature setting, " reduce " used to reduce the temperature setting, Press the "SET" save Settings of data, then the temperature controller to return to control operation. In more than 15 seconds set state not operation will automatically save Settings data and returns status.Of actual use please do not set the limit higher than the upper.Temperature sensor short-circuit, open circuit fault tip Err.3. Installation: instrument temperature must be held at around -5degree ~ 65degree, the instrument must be placed in no damp and high pressure situation, and ventilation to easy to heat dissipation.
4. Wiring: put the device that need to control inserted in a socket, the power supply must match the manual of the instrument.
5. Parameter:
symbols | Description | range | Default value | |
H1 | The first group High limit | 0-124.9degree | 26degree | |
L1 | The first group Low limit | 25degree | ||
H2 | The second group High limit | 32degree | ||
L2 | The second group Low limit | 30degree | ||
HH | Need to customize | High alarm limit | 1-124.9degree | 95degree |
LL | Low alarm limit | 0-124.9degree | 10degree | |
HC1 | Group 1 Cooling/heating switches | 00~70 | 00 | |
HC2 | Group 2 Cooling/heating switches | 00~70 | 01 |
Note: HC heating/cooling state switch data
00 = heating,01= cooling Other values are not output
HMWST-C2 type intelligent temperature controller